– Single-phase uninterruptible power supplies
– On-line double conversion with DSP tecnology (Digital Signal Processor)
– MISSION UPS is equipped with a LCD display to shows all parameters (more than 50 items), and is possible to set the most basic configurations directly on LCD display
– MISSION is a compact UPS, and can be used for all kind of applications
– It is a true on-line transformerless UPS, double conversion technology, single phase
– It includes a maintenance bypass (6KVA and 10KVA models), and it is possible to increase the back-up time by adding battery packs
– MISSION is the most suitable product for critical loads
– It has 0 ms switching time and guarantee a perfect protection for all applications requiring an input voltage without disturbances and no interruptions
– A PF at 0.9 and DSP technology (Digital Signal Processor) it provides high output efficiency for all kind of loads

Features
– High input and output PF
– Wide input voltage range (energy saving)
– Eco Mode (Economic operation mode)
– Back feed protection and Surge Protection – Auto self test
– Cold Start
– Parallel operation capability
– Output By-pass
– Additional battery pack
– USB
– EPO
– Software included
– Intelligent Slot SNMP board (optional) – Dry contact (optional)

Specifications
– Nominal Power: 3000 VA / 2700 W
– Input: Single-phase + GND
– Voltage Range:
* 115 +/- 5VAC
* 295 +/- 5VAC
– Frequency Range:
* 45Hz-55Hz@50HZ
* 55Hz-65Hz@60HZ
– Power Factor: =>0.98
– ECO interval: Output voltage +/- 20 VAC
– Bypass range: 186 VAC – 252 VAC
– THDi: <=7% (100% non linear load) - Connection: 1× Terminal block L/N + T - Output: Single-phase + GND - Nominal Voltage: 208/220/230/240 VAC - Power Factor: 0.9 - Voltage tolerance: +/- 2% - Frequency: * Normal operation: When input frequency is within its range, then output frequency is the same than input; When input frequency is out of its range, then output frequency is (50/60 +/-0.2)Hz, which is the same as in battery mode * Battery operation: (50/60 +/-0.2)Hz - Crest Factor: 3:1 - Switching time: Rete - battery = 0ms - Overload: * Battery operation: ** 108% +/-5% < load <= 150% +/-5% >30s output shutdown and signal
** 150% +/-5% < load < 200% +/-5% >300ms output shutdown and signal
* Normal operation:
** 108% +/-5% < load <=150% +/-5% >30s switch to bypass and signal
** 150% +/-5% < load <200% +/-5% >300ms switch to bypass and signal
– Efficiency:
* Normal operation: 100% of load =>88%
* Battery operation: 100% of load =>85%
* ECO: 100% of load =>94%
– Output voltage distortion:
* <= 3% (100% linear load) * <= 5% (100% non linear load) - Outlet type: 3× IEC, 1× Terminal block L/N + T - Input battery voltage: 72 VDC - Number of internal batteries: 6 - Type of battery: 12V/7AH battery maintenance-free, sealed lead acid (referred to UPS standard only) - Autonomy time: Full load =>4min (referred to UPS standard only), for long autonomy times models, the autonomy is defined by the battery capacity
– Recharge current: 1A
– Environmental conditions:
* Temperature: 0°C – 40°C (battery excluded)
* Humidity: 0 – 95% whitout condensation
* Max Operating altitude: < 1500m; if >1500m, output power reduced
– Storage temperature: -25°C – 55°C (battery excluded)
– Dimensions (W×D×H): 191×469×339 mm
– Weight: 24.6 kg