– FLEXIBLE series can be installed in rack or tower version, it is a true On-line UPS with double conversion tecnology and DSP control (Digital Signal Processor)
– It is possible to increase the back up time with additional battery packs
– USB and RS232 are standard comunications ports, and also RJ45 filter port is available by default
– EPO contact is included and it is possible to use SNMP or RELAY CARD (optional) with Intelligent slot port on the rear panel
– FLEXIBLE is configured with terminal block (input and output), perfectly suitable for every kind of industrial applications
– FLEXIBLE is the best in class UPS with high quality – Its your best choice to protect critical load
Specifications
– Phase: Single phase with ground
– Power: 6000VA / 5400W
INPUT
– Nominal Voltage: 208/220/230/240VAC
– Operating voltage range:
* Low line transfer:
187Vac +/-5% @ 100% – 80% load
160Vac +/-5% @ 80% – 70% load
140Vac +/-5% @ 70% – 60% load
120Vac +/-5% @ 60% – 50% load
110Vac +/-5% @ 50% – 0% load
* Ambient Temp. <35C
* High line transfer: 300Vac +/-5%
* High line comeback: 290Vac +/-5%
- Operating frequency range: 40 - 70 Hz
- Power factor: >0.99@100% load (Nominal Input Voltage)
– Generator input: Supported
OUTPUT
– Output voltage: 208/220/230/240Vac
– Power factor: 0.9
– Voltage regulation: +/- 1%
– Frequency:
* Line Mode (synchronized range): 40 – 70 Hz
* Battery Mode: (50/60 +/-0.1) Hz
– Crest factor: 03:01:00
– Harmonic distortion (THDv):
* <2% THDwith linear load
* <5% THD with non linear load
- Waveform: Pure Sinewave
- Transfer time:
* AC mode <-> Batt. Mode: Zero
* Inverter <-> bypass: 4ms (Typical)
– Efficiency:
* >94% (AC mode)
* >89% (DC mode)
BATTERY
– Battery Type: depends on the capacity of external batteries
– Numbers: 16/20
– 16/20: Long run unit depends on the capacity of external batteries
– Typical recharge time(standard modle): 4 hours recover to 90% capacity (Typical)
– Charging voltage: 137/219.2 VDC +/-1%
– Charge current: 12A max,can be setting by LCD
SYSTEM FEATURES
– Line Mode / Battery Mode:
* Ambient Temp. <35C:
** 105% - 110%: UPS shuts down after 60 minutes at battery mode or transfer to bypass when the utility is normal
** 110% - 130%: UPS shuts down after 5 minutes at battery mode or transfer to bypass when the utility is normal
** >130%: UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal
* 35C
– Short Circuit: Hold Whole System
– Overheating: Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
– Low battery voltage: Alarm and Switch off
– EPO (optional): Shut down UPS immediately
– Audible & Visual alarms: Line Failure, Battery Low, Overload, System Fault
– Comunication interface: USB (or RS232), SNMP Card (optional), Relay Card (optional)
ENVIRONMENTAL
– Operating temperature: 0C to 40C
– Storage temperature: -25C to 55C
– Humidity range: 20-90% RH @ 0- 40C (non-condensing)
– Altitude: <1500m
- Noise level Less than: 50dBA at 1 Meter
PHYSICAL
- Dimension (W×H×D): 440×86×490 mm
STANDARDS
- Safety: IEC/EN62040-1, IEC/EN60950-1
- EMC: IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8
Recenzije